Supplementary Manual CANopen for NORDAC SK 20E

78

Subject to technical amendments

BU 0260 GB

Option monitoring

With the parameter (P120) "Option monitoring", SK 200E series frequency inverters provide the facility for
monitoring connected technology units (SK xU4-…) with regard to their current functional status. Generally,
this function corresponds to monitoring via parameter (P513). Except for the setting { -0.1 } this parameter
(P513) therefore has no effect.

Node Guarding

The Node Guarding function enables the monitoring of the slave(s) by the master.
If after a query by the master, a response is not received from the slave after after a defined time, an error
message is triggered.

The monitoring interval is defined in parameter (P166[-01]) "Timeout control" / "Guard Time".

Life Guarding

The Life Guarding function enables the monitoring of the master by the slave.
If after the receipt of a protocol and the elapse of a defined time the slave does not receive a further protocol
from the master, an error message is triggered.

The monitoring interval is defined by the combination of parameter (P166[-01]) "Timeout control" / "Guard
time" and )P167) "Life time factor".

Heartbeat monitoring

For overriding monitoring, a "Producer Heartbeat time" can be defined. Activation of the parameter (P166 [-
02]) "Timeout control" / "Producer Heartbeat time" by a value ≠ "0" prompts the slave to the cyclic transmission
of a corresponding protocol


6.1.2

EMCY message

In case of faults with frequency inverters connected to the system, the bus module sends an error message
via the CANopen bus. The identifier of the message is 0x80 + address of the bus module. The message is
structured as follows.

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Error code

Parameter

0x1001

FI-ID

0...3

Not used


The assignment of error codes can be found in Section 4.9.6 "Error messages (EMCY message)".

After the error is reset, the Emergency Object is sent with the error message null.
The Transmit ID for the error telegram is based on the following formula:

Node ID

x

D

Transmit I

80

0