Supplementary Manual CANopen for NORDAC SK 20E

38

Subject to technical amendments

BU 0260 GB

The following check list provides and overview for the commissioning of a relevant network.

Description

Designation

Relevant parameter

Comments

Necessary / required settings
Hardware address

Different for each
subscriber (node)

Bus node

CANopen identifier

DIP switch

Frequency inverter

System bus address (CAN)

DIP switch

(SK 200E)

alternative

(P515)

Baud rate

Same for each
subscriber (node)

Bus node

CANopen baud rate

DIP switch

Frequency inverter

System bus baud rate

Fixed at 250kBaud

(SK 200E)

Alternative (P514)

(leave at 250kBaud!)

PDO pause time

Inhibit time

(P163)

PDO transmission interval

Event time

(P164)

Definition of process data (PZD)

STW / ZSW / SW / IW

(P502), (P503), (P509),
(P510), (P546)

(… or (P548))

alternative (P168)
(profile DSP 402)

Additional settings
PDO transmission type

PDO transmission type

(P162)

CAN node monitoring

Guard-time and Heartbeat

(P166) and (P167)

Validity of PDO/SDO

COB-ID On/Off

(P160)

Setting only in special cases (if possible leave at factory setting)
Definition of COB-ID

COB-ID

(P161)

Definition of PZD mapping

PDO mapping

(P165)


For a description of the individual objects please refer to Section 4.9 "Object dictionary".


4.2 EDS file

For CANopen masters which can be configured with a PC, Getriebebau Nord GmbH provides the necessary
EDS file (Electronic Data Sheet) with the relevant CANopen objects for all relevant Nord products. These files
are contained on the documentation CD, which is provided with the hardware. Updates on a daily basis are
available on

www.nord.com

.


4.3 Hardware configuration of the CANopen bus modules

Configuration of the bus module is carried out exclusively via a DIP switch element attached to the module
(see Section 2.2.3 "Configuration"). In addition to the baud rate and the node addresses (node identifiers) the
termination resistors for the bus system and the CANopen bus must be set.
Software configuration if these items is not provided.

NOTE

The coding of the DIP switches (Identifier, address and baud rate) are only read out during
the initialisation phase, i.e. after switching on the 24V power supply to the bus module.
Changes to the DIP switches are therefore only recognised if the module has been
switched off for a sufficient period (all LEDs out) after a change of addressing.