5 Parameterisation

BU 0260 GB

Subject to technical amendments

69

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P162

... [-01]

...

...

[-10]

PDO transmission type

0 ... 255

{ 255 }

Setting of transmission type.
(see objects 1400

(hex)

…1404

(hex)

and 1800

(hex)

…1804

(hex)

, each Sub-index 2)

[-01] = PDO1 TX

(FI 1)

[-02] = PDO1 RX

(FI 1)

[-03] = PDO2 TX

(FI 2)

[-04] = PDO2 RX

(FI 2)

[-05] = PDO3 TX

(FI 3)

[-06] = PDO3 RX

(FI 3)

[-07] = PDO4 TX

(FI 4)

[-08] = PDO4 RX

(FI 4)

[-09] = PDO5 TX

(bus module)

[-10] = PDO5 RX

(bus module)

P163

... [-01]

...

...

[-05]

TxPDO Inhibit time

0 ... 3276.7 ms

{ 10.0 }

Determines the minimum interval between the transmission of the same COB-IDs.
(see objects 1800

(hex)

…1804

(hex)

, each Sub-index 3)

[-01] = PDO1

(FI 1)

[-02] = PDO2

(FI 2)

[-03] = PDO3

(FI 3)

[-04] = PDO4

(FI 4)

[-05] = PDO5

(bus module)

P164

... [-01]

...

...

[-05]

TxPDO Event time

0 ... 32767 ms

{ 250 }

Defines a time interval, after which the process data (PDO) are transmitted.
(see objects 1800

(hex)

…1804

(hex)

, each Sub-index 5)

[-01] = PDO1

(FI 1)

[-02] = PDO2

(FI 2)

[-03] = PDO3

(FI 3)

[-04] = PDO4

(FI 4)

[-05] = PDO5

(bus module)

0 = "OFF"