Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P167

Life time factor

0 ... 255

{ 0 }

Factor for the monitoring of the master by the slave
(see objects 100D

(hex)

)


0 = "OFF"

P168

... [-01]

...

...

[-17]

Profile parameters

0 ... 3FFF

(hex)

{see table on right}

Parameter setting for the profile parameters (Velocity Mode of the drive profile DSP 402).
(see objects 6048

(hex)

and 6049

(hex)

, each Sub-index 1 - 2)

Acceleration and deceleration
This results in the unit: rpm/s

(achieved change in [rpm] divided by the time elapsed during the change in [s])

Array

[-01] = Profile:

0= "OFF"
1= "ON"

[-02] = ∆n for acceleration FI 1

[-03] = ∆t for acceleration FI 1

[-04] = ∆n for deceleration FI 1

[-05] = ∆t for deceleration FI 1

[-06] = ∆n for acceleration FI 2

[-07] = ∆t for acceleration FI 2

[-08] = ∆n for deceleration FI 2

[-09] = ∆t for deceleration FI 2

Factory setting

{ 0 }


{ 1500 }

{ 2 }

{ 1500 }

{ 2 }

{ 1500 }

{ 2 }

{ 1500 }

{ 2 }

Array

[-10] = ∆n for acceleration FI 3

[-11] = ∆t for acceleration FI 3

[-12] = ∆n for deceleration FI 3

[-13] = ∆t for deceleration FI 3

[-14] = ∆n for acceleration FI 4

[-15] = ∆t for acceleration FI 4

[-16] = ∆n for deceleration FI 4

[-17] = ∆t for deceleration FI 4

Factory setting

{ 1500 }

{ 2 }

{ 1500 }

{ 2 }

{ 1500 }

{ 2 }

{ 1500 }

{ 2 }

Units:

∆n in [rpm]
∆t in [ms]