Supplementary Manual CANopen for NORDAC SK 20E

24

Subject to technical amendments

BU 0260 GB

2.2.2.2 Control connections of the SK CU4-CAO(-...)

The double spring-loaded terminal bar of the technology unit is colour coded, and therefore indicates the
three different potential levels.
A separate power source should be used particularly for the supply of the DOs. However, by bridging the
24V o and GND o to one of the terminals of the system bus level (24V and GND) it is possible to implement
the supply of the DOs. However, in this case it should be noted that there is an increased risk of introducing
interference into the bus cables.
Connection of up to 4 sensors and 2 actuators is made via the terminal bar. Alternatively, the SK
TU4-CAO-M12 enables the connection of these I/Os via the M12 round plug connector (5 pin socket, A-coded)
mounted on the front.

Double use

of the inputs via the terminal bar and the M12 round plug connector must be avoided.

field bus level

CANopen

System bus level and digital inputs

Digital outputs

24V-B

CAO

CAO+

IN

CAO-

IN

GND B

CAO

SHLD

24V

24V

(as 11)

GND

GND

DIN 1

GND

24V

(as 11)

DIN 2

GND

24V

(as 11)

24V

O

DO

DO 1

GND

O

DO

1

3

5

7

9

11

13

15

17

19

21

23

25

27

29

31

33

35

2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

24V-B

CAO

CAO+

OUT

CAO-

OUT

GND B

CAO

PE

24V

(as 11)

Sys +

Sys -

GND

DIN 3

GND

24V

(as 11)

DIN 4

GND

24V

(as 11)

GND

O

DO

DO 2

GND

O

DO



Connection example: SK TU4-CAO to SK 200E

SK205E… - connection unit (SK TI4...)

SK TU4-CAO… - connection unit (SK TI4-TU-BUS)

Voltage

source

24V DC

CANopen

subscriber

X-1

Voltage

source

24V DC

CANopen

subscriber

X+1

NOTE

In principle, looping of the 24V supply voltage (terminals 1/2) or also e.g.: (terminals 11/15)
is possible, however a maximum permissible current load of 3A for the
SK TU4-CAO(-…)must not be exceeded.

Illustration of the terminal bar of the bus connection unit
SK T14-TU-BUS with allocation of functions

Potential level: field bus

Potential level: system bus

Potential level: DOs