11 i-1011: restore default parameters, 11 i−1011: restore default parameters, Implemented canopen objects – Lenze EMF2178IB User Manual
Page 102
Implemented CANopen objects
Overview
I−1011: Restore default parameters
l
102
EDSMF2178IB EN 3.0
13.2.11
I−1011: Restore default parameters
Loading of Lenze settings
)
Note!
For this function, the subindices to be used depend on the controller type.
Index (hex)
0x1011
Name
Restore default parameters
Subindex
Default
setting
Value range
Access
Data type
0
Restore default
parameters
−
0
...
2
32
− 1 ro
U32
1
rw
U32
...
7
Subindices
Subindex
Authorisati
on
Description
Write
Read
0
ro
While writing, the 0x06010002 error
message occurs.
Max. available subindex (depending on
standard device):
l
93xx : 3
l
ECSXX: 3
l
82vector : 7
l
82xx: 5
1
rw
All parameters can be loaded
2
This function is not supported.
While writing, the 0x08000020 error
message occurs.
Only object communication parameters
can be loaded
3
Only manufacturer−specific parameters
can be loaded
(Index 0x6000 ... 0x9FFF)
4
Parameter set 1 can be loaded
5
Parameter set 2 can be loaded
6
Parameter set 3 can be loaded
7
Parameter set 4 can be loaded