2 led status displays, Diagnostics – Lenze EMF2178IB User Manual

Page 89

Advertising
background image

Diagnostics

LED status displays

12

l

89

EDSMF2178IB EN 3.0

12.2

LED status displays

The LEDs on the front are provided to the communication module for the purpose of fault
diagnostics.

2172CAN000D

Fig. 12−1

LEDs of the communication module

Pos.

Status display (LED)

Description

0

Connection status to standard device, two−colour LED (green/red)
OFF

l

The communication module is not supplied with voltage.

l

The external voltage supply is switched off.

GREEN

Blinking

The communication module is supplied with voltage, but has no
connection to the standard device.
Cause:
The standard device is ...

l

switched off;

l

in the initialisation phase;

l

not available.

Constantly ON

The communication module is supplied with voltage and is
connected to the standard device.

RED

Constantly ON

CANopen operation impossible.

Blinking

Permanently:

l

Parameters are reset to Lenze setting.

l

CANopen operation possible.

1 x blinking:

l

An error occurred while saving a value.

2 x blinking:

l

CANopen operation possible.

l

The node address/baud rate from C1850/C2350 or C1851/C2351
could not be accepted .