18 i-1200/i-1201: server sdo parameters, 18 i−1200/i−1201: server sdo parameters, Implemented canopen objects – Lenze EMF2178IB User Manual

Page 107

Advertising
background image

Implemented CANopen objects

Overview

I−1200/I−1201: Server SDO parameters

13

l

107

EDSMF2178IB EN 3.0

13.2.18

I−1200/I−1201: Server SDO parameters

Server SDOs can be parameterised with two objects:

ƒ

I−1200 for the parameter data channel 1 (SDO1)

ƒ

I−1201 for the parameter data channel 2 (SDO2)

With I−1201 the identifier can be written in sending and receiving direction, I−1200 has only
got reading access. The server SDO parameters are only valid, if bit 31 = "0" in both
transmission directions (subindex 1 and 2).

Index

Subindex

Name

Data type

Value range

Authorisatio
n

I−1200

0

Server SDO1 parameters

U8

0 ... 255

ro

1

Identifier
Client

® server (rx)

U32

0 ... (2

32

− 1)

ro

2

Identifier
Server

® client (tx)

U32

0 ... (2

32

− 1)

ro

I−1201

0

Server SDO2 parameters

U8

0 ... 255

ro

1

Identifier
Client

® server (rx)

U32

0 ... (2

32

− 1)

rw

2

Identifier
Server

® client (tx)

U32

0 ... (2

32

− 1)

rw

Subindices

Subindex

Description

0

Max. supported subindex = 3

1

Specification of the receive identifier

2

Specification of the transmit identifier

Data telegram assignment for subindex 1 and 2

Byte 8

7th byte

Byte 6

Byte 5

MSB

U32

LSB

31

30

29

28

...

11

10

...

0

0/1

0

0

Bit value: 0

11−bit identifier

Bits

Value

Description

0 ... 10

X

11−bit identifier

11 ... 29

0

The extended identifier is not supported. Any of these bits must be "0".

30

0

Reserved

31

0

SDO valid

1

SDO invalid

Advertising