Process data transfer – Lenze EMF2178IB User Manual

Page 66

Advertising
background image

Process data transfer

Cyclic process data objects
Mapping in CANopen objects (I−160x, I−1A0x)

9

l

66

EDSMF2178IB EN 3.0

AIF data image in codes

The AIF process data images are mapped to the following codes:

AIF process data

Code

Index
[hex]

Process input data AIF−IN as 16−bit values

C1822/1 ... 12

0x58E1

Process output data AIF−OUT as 16−bit values

C1823/1 ... 12

0x58E0

Process input data AIF−IN as 32−bit values

C1824/1 ... 11

0x58DF

Process output data AIF−OUT as 32−bit values

C1825/1 ... 11

0x58DE

The codes represent the values at the AIF interface. Converted into indices, mapping refers
to these codes.

Process data AIF−IN

Represented as

16−bit values

32−bit values

1)

Byte 1

AIF1−IN
(bytes 1 ... 8)

C1822/1

[C1824/1]

2nd byte

3rd byte

C1822/2

C1824/2

Byte 4

Byte 5

C1822/3

C1824/3

Byte 6

7th byte

C1822/4

[C1824/4]

Byte 8

Byte 9

AIF2−IN
(bytes 1 ... 8)

C1822/5

C1824/5

Byte 10

Byte 11

C1822/6

[C1824/6]

Byte 12

Byte 13

C1822/7

[C1824/7]

Byte 14

Byte 15

C1822/8

[C1824/8]

Byte 16

Byte 17

AIF3−IN
(bytes 1 ... 8)

C1822/9

C1824/9

Byte 18

Byte 19

C1822/10

[C1824/10]

Byte 20

Byte 21

C1822/11

[C1824/11]

Byte 22

Byte 23

C1822/12

Byte 24

1)

[Cxxx/y] = Codes not relevant for the AIF modes

(

68)

Advertising