Commissioning

Setting node address and baud rate

6

l

35

EDSMF2178IB EN 3.0

Baud rate setting

1 2 3 4 5 6 7 8 910

OPEN

ON

OFF

Bd

Address

Fig. 6−2

Baud rate setting

ƒ

The baud rate must be the same for all CAN nodes.

ƒ

The following baud rates can be set:

Baud rate [kbps]

Switch

8

9

10

10

ON

ON

OFF

20

ON

OFF

ON

50

OFF

ON

ON

125

OFF

ON

OFF

250

OFF

OFF

ON

500

OFF

OFF

OFF

1000

ON

OFF

OFF

)

Note!

Switch off the voltage supply of the communication module, and then switch
it on again to activate the changed settings.