Commissioning

Setting node address and baud rate

6

l

34

EDSMF2178IB EN 3.0

Node address setting

1 2 3 4 5 6 7 8 910

OPEN

ON

OFF

Bd

Address

Fig. 6−1

Address assignment via DIP switch

ƒ

If several devices are connected to the CAN network, the node addresses must differ
from each other.

ƒ

The desired node address results from the sum of the values of switches (1 ... 7) in
ON position.

Switch

Value

Example

Switch position

Node address

1

64

OFF

16 + 4 + 2 + 1 = 23

2

32

OFF

3

16

ON

4

8

OFF

5

4

ON

6

2

ON

7

1

ON

)

Note!

Switch off the voltage supply of the communication module, and then switch
it on again to activate the changed settings.