Codes – Lenze EMF2178IB User Manual

Page 133

Advertising
background image

Codes

Communication−relevant Lenze codes

14

l

133

EDSMF2178IB EN 3.0

C1860:
Display of the current DIP switch position

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1860

22715 =
0x58BB

g

U16

By displaying the current DIP switch position it is possible to find out if the switch position
for node address and baud rate has changed since the last initialisation.

DIP switch valencies

Switch

1

2

3

4

5

6

7

8

9

10

Value

512

256

128

64

32

16

8

4

2

1

Bit

15 ... 10

9

8

7

6

5

4

3

2

1

0

Example for DIP switch position

ƒ

Switches 3, 5, 6, 7 = ON (address 23)

ƒ

Switches 8, 9, 10 = OFF (baud rate 500 kbit/s)
The sum of the corresponding valencies "0xB8" (184) is displayed when code
C1859/C2359 is read.

C1861:
Display of the active CAN node address

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1861

22714 =
0x58BA

g

FIX32

Display of the CAN node address active on the CAN bus.

C1862:
Display of the active baud rate

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1862

22713 =
0x58B9

g

0:
1:
2:
3:
4:
5:
6:

500 kbps
250 kbps
125 kbps
50 kbps
1000 kbps
20 kbps
10 kbit/s

FIX32

Display of the baud rate active on the CAN bus.