Codes

Communication−relevant Lenze codes

14

l

138

EDSMF2178IB EN 3.0

C1873/C2373:
Sync rate CAN−IN1 ... 3

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1873

/1: CAN−IN1
/2*: CAN−IN2
/3*: CAN−IN3

22702 =
0x58AE

1

0

[1]

240 FIX32

C2373

22202 =
0x56BA

*) not effective when using 8200 vector or 93XXcontrollers

The process input data (CAN−INx) are only transferred to the controller after a certain
number of sync telegrams have been received.

The sync rate can be set individually for each input PDO.

)

Note!

Only sync telegrams are counted that have been received with the identifier
set under code C1867/C2367 of the communication module.

Example:

ƒ

Selection n = 23:
Acceptance of input PDO (to CAN−IN1 ... 3) into the controller after arrival of the 23rd
sync telegram.

Relation to CANopen

The objects I−1400 ... I−1402 (Receive PDO Communication Parameters), subindex 2 each
(transmission type), are mapped on the corresponding subcodes of C1873/C2373 in the
value range 1 ... 240.

Exception: Object I−140X, subindex 2 = "254" is mapped manufacturer−specifically as
value "0" on the corresponding subcodes of C1873/C2373.

Object I−140X, subindex

Mapping to code / subcode

I−140X, subindex 2 = 1 ... 240

C1873, subcode X = 1 ... 240

I−140X, subindex 2 = 254

C1873, subcode X = 0