2 mapping in canopen objects (i-160x, i-1a0x), Mapping in canopen objects (i−160x, i−1a0x), Process data transfer – Lenze EMF2178IB User Manual

Page 65

Advertising
background image

Process data transfer

Cyclic process data objects

Mapping in CANopen objects (I−160x, I−1A0x)

9

l

65

EDSMF2178IB EN 3.0

9.3.2

Mapping in CANopen objects (I−160x, I−1A0x)

General

)

Note!

Mapping is not possible in communication modules used together with old
devices of the 8200 series.

The CANopen objects I−160x and I−1A0x are used to assign the CANopen process data to the
internal data. In the EMF2178IB communication module an assignment to the process
data of the internal AIF interface is possible. The process data volume and type depends on
the standard device.

The process data length depends on the AIF mode (

^ 68):

Basic device

AIF mode

8200 vector

Mode 3: 3 process data words with variable assignment

93XX

Mode 4: 4 process data words with variable assignment

9300 servo PLC

Mode 5: 12 process data words with variable assignment

ECSXX

depends on the variant (mode 4 or 5)

For mapping in the module, the master enters indices and data lengths.

Mapping structure

MSB

LSB

31

...

16 15

...

8 7

...

0

Index

Subindex

Object length

DWord 0 = 0x20

Word = 0x10

The EDS file for the EMF2178IB communication module supports the mapping.

I

Tip!

The current EDS file required for configuring the EMF2178IB (CANopen)
communication module can be found in the download area on:
www.Lenze.com

Advertising