Data transfer – Lenze EMF2178IB User Manual

Page 43

Advertising
background image

Data transfer

Structure of the CAN telegram

8

l

43

EDSMF2178IB EN 3.0

Identifier (COB−ID)

The principle of the CAN communication is based on a message−oriented data exchange
between a transmitter and various receivers. Here, all nodes can quasi simultaneously
transmit and receive messages. In case of CANopen, a node orientation is achieved by
having only one transmitter for each message.

The control which node is to receive a transmitted message is executed via the identifierin
the CAN telegram, also called COB−ID(Communication Object Identifier). In addition to the
addressing, the identifier contains information on the priority of the message and the type
of user data.

With the exception of the network management and the sync telegram, the identifier
consists of a basic identifier and the node address of the node to be addressed:

Identifier (COB−ID) = basic identifier + adjustable node address (Node−ID)

The identifier assignment is defined in the CANopen protocol.

Basic identifier

The basic identifier is preset as default with the following values according to the CANopen
specification:

Object

Direction

Basic identifier

from the drive

to the drive

dec

hex

NMT

0

0x000

Sync

128

0x080

Emergency

X

128

0x080

PDO1
(Process data channel 1)

TPDO1

X

384

0x180

RPDO1

X

512

0x200

PDO2
(Process data channel 2)

TPDO2

X

640

0x280

RPDO2

X

768

0x300

PDO3
(process data channel 3)

TPDO3

X

896

0x380

RPDO3

X

1024

0x400

SDO1
(Parameter data channel 1)

X

1408

0x580

X

1536

0x600

SDO2
(parameter data channel 2)
Lenze setting: not active.

X

1472

0x5C0

X

1600

0x640

Node guarding / heartbeat

X

1792

0x700

Node address (node ID)

Each node of the CAN network must be assigned with a node address (also called node ID)
within the valid address range for unambiguous identification.

ƒ

A node address must not be assigned more than once within a network.

ƒ

The node address of the controller is configured under code C1850/C2350 or via DIP
switch(