Codes – Lenze EMF2178IB User Manual

Page 127

Advertising
background image

Codes

Communication−relevant Lenze codes

14

l

127

EDSMF2178IB EN 3.0

Identifier for selective addressing via C1854/C2354

In case of this addressing, the identifier is the sum of a fixed basic identifier 384 (0x180) +
the value of the corresponding subcode of C1854/C2354. Here, the node address has no
influence anymore.

This configuration has been created in accordance with 8200 vector controllers with
E82ZAFCCxxx function module (system bus (CAN)) and the integrated system bus
interface of the 93XX controllers (code C0353/C0354, selective addressing).

PDO

Identifier for addressing via C1854/C2354

C1853/C2353 = 1

C1853/C2353 = 1
(with Lenze setting)

CAN−IN1

384 + C1854/1 or 384 + C2354/1

384 + 129

0x201

CAN−IN2

384 + C1854/3 or 384 + C2354/3

384 + 257

0x281

CAN−IN3

384 + C1854/5 or 384 + C2354/5

384 + 385

0x301

CAN−OUT1

384 + C1854/2 or 384 + C1854/2

384 + 1

0x181

CAN−OUT2

384 + C1854/4 or 384 + C1854/4

384 + 258

0x282

CAN−OUT3

384 + C1854/6 or 384 + C1854/6

384 + 386

0x302

Identifier for addressing to Lenze system bus

This setting corresponds to the preset calculation of the identifiers for 8200 vector
controllers in connection with an E82ZAFCCxxx function module (system bus (CAN)) and
the integrated system bus interface of 93XX controllers.

The identifier once again consists of a basic identifier and the node address.

PDO

Identifier for addressing via Lenze system bus (CAN)

C1853/C2353 = 2

CAN−IN1

512 + node address

0x200 + node address (hex)

CAN−IN2

640 + node address

0x280 + node address (hex)

CAN−IN3

768 + node address

0x300 + node address (hex)

CAN−OUT1

384 + node address

0x180 + node address (hex)

CAN−OUT2

641 + node address

0x281 + node address (hex)

CAN−OUT3

769 + node address

0x301 + node address (hex)

Advertising