4 error codes, Parameter data transfer – Lenze EMF2178IB User Manual

Page 76

Advertising
background image

Parameter data transfer

Error codes

10

l

76

EDSMF2178IB EN 3.0

10.4

Error codes

Error code
[hex]

Description

0x05030000

Toggle bit not changed

0x05040000

SDO protocol expired

0x05040001

Invalid or unknown client/server command specifier

0x05040002

Invalid block size (only block mode)

0x05040003

Invalid processing number (only block mode)

0x05040004

CRC error (only block mode)

0x05040005

Not enough memory

0x06010000

Object access not supported

0x06010001

Try to read writable object

0x06010002

Try to write readable object

0x06020000

Object not listed in object directory

0x06040041

Object not mapped to PDO

0x06040042

Number and length of objects to be transferred longer than PDO.

0x06040043

General parameter incompatibility

0x06040047

General internal controller incompatibility

0x06060000

Access denied because of hardware error

0x06070010

Inappropriate data type, service parameter length

0x06070012

Inappropriate data type, service parameter length exceeded

0x06070013

Inappropriate data type, service parameters not long enough

0x06090011

Subindex does not exist

0x06090030

Parameter value range exceeded

0x06090031

Parameter values too high

0x06090032

Parameter values too low

0x06090036

Maximum value falls below minimum value

0x08000000

General error

0x08000020

Data cannot be transferred or stored for the application.

0x08000021

Because of local control, data cannot be transferred or stored for the application.

0x08000022

Because of current controller status, data cannot be transferred or stored for the
application.

0x08000023

Dynamic generation of object directory not successful or no object directory available
(e.g. object directory generated from file, generation not possible because of a file
error).