Lenze parameter sets

Parameter sets for 8200 vector controller

10

l

71

EDSMF2178IB EN 3.0

10.2

Lenze parameter sets

Parameter sets are used for separately storing codes based on the need for different
configurations of application processes.

(

Stop!

8200 vector with EMF2178IBcommunication module

ƒ

The cyclic writing of parameter data to the EEPROM is not permissible.

ƒ

If you still want to change parameter data, code C0003 must be set to "0"
after every mains switching. The parameter data are not stored in the
EEPROM but as volatile data.

10.2.1

Parameter sets for 8200 vector controller

The 8200 vector controller has four parameter sets the parameters of which can be directly
addressed via the INTERBUS.

Addressing

Addressing is carried out with a code offset:

ƒ

Offset "0" addresses the parameter set 1 with the codes C0000 ... C1999.

ƒ

Offset "2000" addresses the parameter set 2 with the codes C2000 ... C3999.

ƒ

Offset "4000" addresses the parameter set 3 with the codes C4000 ... C5999.

ƒ

Offset "6000" addresses the parameter set 4 with the codes C6000 ... C7999.

If a parameter is only available once (see documentation of the controller), use the code
offset "0".

Example

Addressing of the code C0011 (maximum field frequency) in different parameter sets:

ƒ

C0011 in parameter set 1: Code no. = 11

ƒ

C0011 in parameter set 2: Code no. = 2011

ƒ

C0011 in parameter set 3: Code no. = 4011

ƒ

C0011 in parameter set 4: Code no. = 6011

)

Note!

Automatic saving of the changed parameter data is activated (Lenze basic
setting, can be switched off via C0003).