Implemented CANopen objects

Overview

I−1015: Emergency inhibit time

13

l

105

EDSMF2178IB EN 3.0

13.2.13

I−1015: Emergency inhibit time

Index (hex)
0x1015

Name
Emergency inhibit time

Subindex

Default
setting

Value range

Access

Data type

0

0

0

...

65535 rw

U16

This object determines the time between two emergency telegrams.

The value entered is multiplied by 0.1, the result is the delay time in milliseconds.

13.2.14

I−1016: Consumer heartbeat time

Index (hex)
0x1016

Name
Consumer heartbeat time

Subindex

Default
setting

Value range

Access

Data type

0

Consumer heartbeat time 0

0

...

65535 ro

U32

1

rw

U32

Subindices

Subindex

Explanation

0

Highest subindex

1

Node ID and "heartbeat time" of node

Bit assignment, subindex 1

U32

31 ... 24

23 ... 16

15 ... 0

Reserved, value 0

Node ID

Heartbeat time [ms]

The "consumer heartbeat time" is used to monitor a node.

The "consumer heartbeat time" must be longer than the "producer heartbeat time" of the
node to be monitored.

If the selected time is exceeded, the communication module will send an emergency
telegram including the "heartbeat error" 0x8130.

Under code C1882/subcode 5, you can set the response of the basic device.