Monitoring

Heartbeat Protocol

11

l

84

EDSMF2178IB EN 3.0

Heartbeat transmission

The heartbeat transmission is activated by entering a time under in the CANopen object
I−1017. The monitoring is activated by setting a time and a node ID in the object I−1016/1.

Telegram structure

NMT identifier plus node ID and a data byte with status information:

Data value (s)

Status

4

Stopped

5

Operational

127

Pre−operational

Identifier

Identifier = Basisadresse (1792) + configurable address (1 ... 127)

Heartbeatmonitoring

The consumer monitors whether the message is received within the "heartbeat consumer
time". If this is not the case, an emergency telegram with a "heartbeat event" is sent.

The controller response to a "heartbeat event" is set under subcode C1882/5 / C2382/5.

If the "heartbeat event" occurs, the node changes from the "Operational" state to the
"Pre−operational" state (default setting). By means of the object I−1029 a different
response can be set.

The heartbeat monitoring only starts when the first heartbeat telegram of a node
monitored has been successfully received and the "Pre−operational" NMT state has been
reached.

I

Tip!

Detailed information on the objects I−1016, I−1017 and I−1029 can be found in
the chapter entitled "Implemented CANopen objects" (

^ 91).