Implemented CANopen objects
Overview
I−1400 ... I−1402: Receive PDO communication parameters
l
110
EDSMF2178IB EN 3.0
Description of subindex 2
PDO transmission
Transmission type
Description
cyclic
synchronous
event−control
led
X
X
n = 1 ... 240
By entering value n, this RPDO will be
accepted by every n−th sync.
X
n = 254
Manufacturer−specific,
see code C1875 / C2375
Description of subindex 5
The "monitoring time" describes the period of time in which new process input data must
arrive with the CAN−IN1 ... 3 identifiers. If the time entered is exceeded, it is possible to set
a corresponding reaction under code C1882.
)
Note!
ƒ
The monitoring time starts with the arrival of the first telegram.
ƒ
Subindex 5 = 0: Monitoring deactivated.