Implemented canopen objects – Lenze EMF2178IB User Manual

Page 113

Advertising
background image

Implemented CANopen objects

Overview

I−1800 ... I−1802: Transmit PDO communication parameters

13

l

113

EDSMF2178IB EN 3.0

Description of subindex 1

Data telegram assignment

Byte 8

7th byte

Byte 6

Byte 5

MSB

U32

LSB

31

30

29

28

...

11

10

...

0

0/1

0/1

0

Bit value: 0

11−bit identifier

Bits

Value

Description

0 ... 10

X

11−bit identifier

11 ... 29

0

The extended identifier is not supported. Any of these bits must be "0".

30

0

RTR to TPDO possible (Lenze)

1

RTR to TPDO not possible (cannot be set)

31

0

TPDO active

1

TPDO not active

Description of subindex 2

PDO transmission

Transmission type

Description

cyclic

synchronous

event−control
led

X

X

n = 1 ... 240

By entering value n, this TPDO will be
accepted by every n−th sync.

X

n = 252

By sync, TPDO will be filled with new
data, but only sent on RTR.

X

n = 254

Manufacturer−specific,
see code C1875 / C2375

Description of subindex 3

Minimum time between two process data telegrams.

)

Note!

Subindex 3 = 0: Inhibit time deactivated.

Description of subindex 5

With event−controlled/cyclic operation, you can set the cycle time for sending PDOs via the
CAN bus.

)

Note!

Subindex 5 = 0: Cyclic PDO sending deactivated.