Codes

Communication−relevant Lenze codes

14

l

126

EDSMF2178IB EN 3.0

C1853/C2353:
Addressing CAN−IN/OUT

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1853

/1: CAN−IN1/CAN−OUT1
/2: CAN−IN2/CAN−OUT2
/3: CAN−IN3/CAN−OUT3

22722 =
0x58C2

0

see table below

FIX32

C2353

22222 =
0x56CE

Possible settings

Selection

Description

0

Addressing to CANopen (default identifier)

1

Addressing to C1854/C2354 (selective addressing)

2

Addressing to Lenze system bus (CAN)

3

Addressing to CANopen objects I−140X/I−180X

Via this code, the source for the resulting addresses of the CAN−INx/OUTx process data
objects (PDOs) on the CAN bus is selected.

Relation to CANopen

The addressing of the corresponding PDP pair or subcode in code C1853/C2353 is switched
to the objects I−140X/I−180X (see above: Selection "3") if a new value is entered into the
objects I−1400 ... I−1402 or I−1800 ... I−1802.

Identifier for addressing to CANopen (default identifier)

This is the Lenze setting of the EMF2178IB communication module. The calculation
consists of the basic identifier and the node address. The basic identifier corresponds to the
preset value according to DS301 V4.02.

PDO

Identifier

C1853/C2353 = 0: Addressing following CANopen (basic identifier)

CAN−IN1

512 + node address

0x200 + node address

CAN−IN2

768 + node address

0x300 + node address

CAN−IN3

1024 + node address

0x400 + node address

CAN−OUT1

384 + node address

0x180 + node address

CAN−OUT2

640 + node address

0x280 + node address

CAN−OUT3

896 + node address

0x380 + node address