3 emergency telegram, Monitoring – Lenze EMF2178IB User Manual

Page 87

Advertising
background image

Monitoring

Emergency telegram

11

l

87

EDSMF2178IB EN 3.0

11.3

Emergency telegram

An emergency telegram is sent once to the master if the error status of the communication
module changes, i.e.

ƒ

if an internal communication module error occurs.

ƒ

if an internal communication module error is eliminated.

The emergency telegram sent via the CAN bus is structured as follows:

ƒ

Byte 1 + 2: Emergency error code

ƒ

Byte 3: Error register object I−1001

ƒ

Bytes 4 ... 8: Field for manufacturer−specific error messages
Contents:
– Emergency error code 0x1000: Lenze error number
– All other emergency error codes have the value "0".

Emergency error
codes
[hex]

Cause

Error register entry
(I−1001)

0x0000

One of several errors eliminated

xx

Single error eliminated
(no more errors)

00

0x1000

Basic device in TRIP, message, warning, FAIL, QSP or persistent fault

01

0x3100

Supply voltage of basic device faulty or failed

01

0x6280

Fault in mapping table with operation with a profile implemented in
the PLC

01

0x8100

Communication error (warning)

11

0x8130

"Life guard error" or "heartbeat error"

11

0x8210

PDO length shorter than expected

11

0x8220

PDO length longer than expected

11

0x8700

Sync telegram monitoring

11