Codes
Communication−relevant Lenze codes
l
123
EDSMF2178IB EN 3.0
C1850/C2350:
CAN node address
Code
Subcode
Index
Possible settings
Data type
Lenze
Selection
C1850
−
22725 =
0x58C5
1
1
[1]
99 FIX32
C2350
−
22225 =
0x56D1
This code serves to set the CAN node address of the communication module.
)
Note!
ƒ
If several CAN nodes are interconnected, their node addresses must differ
from each other.
ƒ
Node addresses > 99 can only be set via DIP switch(
¶ 33).
ƒ
All DIP switches 1 ... 7 = OFF (Lenze setting):
– When the device is switched on, the settings under code C1850/C2350
(node address) and C1851/C2351 (baud rate) are active.
– Code C1850/C2350 is an image of code C0009 of the basic device. Setting
C1850/C2350 has a direct effect on C0009.