Installation

Electrical installation
Bus cable length

5

l

28

EDSMF2178IB EN 3.0

5.2.5.2

Segment cable length

The segment cable length is determined by the cable cross−section used and by the number
of nodes. Repeaters divide the total cable length into segments. If no repeaters are used,
the segment cable length is identical to the total cable length.

Max. number of
nodes per segment

Cable cross−section
(can be interpolated)
0.25 mm

2

(AWG24)

0.5 mm

2

(AWG21)

0.75 mm

2

(AWG19)

1.0 mm

2

(AWG18)

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

100

150 m

270 m

410 m

600 m

Tab. 5−2

Segment cable length

Example: Selection help

Given

Total cable length to be implemented

200 m

Number of nodes

63

Results

Max. possible baud rate

250 kbps
(derived from Tab. 5−1 Total cable length)

Required cable cross−section (interpolated)

0.30 mm

2

(AWG23)

(derived from Tab. 5−2 Segment cable length)

Cable cross−section of standard CAN cable

0.34 mm

2

(AWG22)

(see specification of the transmission cable

^ 26)