1 access to the codes of the controller, Parameter data transfer – Lenze EMF2178IB User Manual

Page 70

Advertising
background image

Parameter data transfer

Access to the codes of the controller

10

l

70

EDSMF2178IB EN 3.0

10.1

Access to the codes of the controller

When using Lenze communication modules, you can change the features and response
characteristics of any controller connected to the network using a higher−level host
system(PLC, master).

In Lenze controllers, parameters to be changed are listed under codes.

Controller codes are addressed via the index when accessing the code through the
communication module.

The index for Lenze code numbers is between 16576 (0x40C0) and 24575 (0x5FFF).

,

Documentation for the controller

Here you can find a detailed description of the codes.

Indexing of Lenze codes

Conversion formula

Index (dec)

Index (hex)

24575 − Lenze code

0x5FFF − (Lenze code)

hex

Example for C0001 (operating mode)

Index (dec)

Index (hex)

24575 − 1 = 24574

0x5FFF − 1 = 0x5FFE

The parameter value is part of the telegram user data (see examples,

^ 77).