Codes
Communication−relevant Lenze codes
l
124
EDSMF2178IB EN 3.0
C1851/C2351:
Baud rate
Code
Subcode
Index
Possible settings
Data type
Lenze
Selection
C1851
−
22724 =
0x58C4
0
0 ... 4
0: 500 kbps
1: 250 kbps
2: 125 kbps
3: 50 kbps
4: 1000 kbit/s
FIX32
C2351
−
22224 =
0x56D0
This code serves to set the baud rate of the communication module.
ƒ
The baud rate must be the same for all CAN nodes.
ƒ
The baud rates 10 kbps and 20 kbps can only be selected via DIP switch(
¶ 33).
ƒ
Setting the code (e.g. with GDC via CAN) has a direct effect on the standard device
code C0125.
)
Note!
ƒ
The baud rate must be the same for all CAN nodes.
ƒ
The baud rates 10 kbps and 20 kbps can only be selected via DIP
switch(
¶ 33).
ƒ
All DIP switches 1 ... 7 = OFF (Lenze setting):
– When the device is switched on, the settings under code C1850/C2350
(node address) and C1851/C2351 (baud rate) are active.
– Code C1851/C2351 is an image of code C0125 of the basic drive. Setting
C1851/C2351 has a direct effect on C0125.