Installation – Lenze EMF2178IB User Manual

Page 29

Advertising
background image

Installation

Electrical installation

Bus cable length

5

l

29

EDSMF2178IB EN 3.0

5.2.5.3

Checking the use of repeaters

Compare the values derived from Tab. 5−1 Total cable length (

27) and Tab. 5−2 Segment

cable length (

28).

ƒ

If the sum of the segment cable lengths is smaller than the total cable length to be
implemented, either repeaters must be used or the cable cross−section must be
increased.

ƒ

If the use of repeaters reduces the max. possible total cable length so much that it is
smaller than the total cable length to be implemented, then the cable cross−section
must be increased or less repeaters must be used or the baud rate must be
decreased.

ƒ

The use of a further repeater is recommended as ...
– service interface

Advantage: Trouble−free connection during bus operation is possible.

– calibration interface

Advantage: The calibration/programming unit remains electrically isolated.

Example

Given

Total cable length to be implemented

450 m

Number of nodes

32

Cable cross−section

0.50 mm

2

(AWG 20)

Baud rate

125 kbps

Repeater used

Lenze repeater EMF2176IB

Reduction of the max. total cable length per
repeater (EMF2176IB)

30 m

Results

Max. total cable length

630 m
(see Tab. 5−1 Total cable length (

^ 27))

Max. segment cable length

360 m
(see Tab. 5−2 Segment cable length (

^ 28))

Comparison

The max. segment cable length is smaller than the total cable
length to be implemented.

Conclusion

A repeater must be installed at the determined max. segment
cable length of 360 m.

Results with 1 repeater

Max. total cable length

600 m
(Reduction of the total cable length (

^ 27) by 30 m)

Max. segment cable length

720 m

Comparison

Both the possible total cable length and the segment cable lengths
are larger than the total cable length to be implemented.

Conclusion

1 repeater is sufficient to implement the total cable length of 450
m.

Advertising