Characteristics

Possible settings

Name

Index

Description

Selection

Lenze

100C

h

0 guard_time

0

0

{1 ms}

65535

VAR

UINT16

RW

Ċ

For activating the node
guarding monitoring
function, the maximum time
between two remote
requests from the master is
parameterised. The
controller calculates this
time from the product of
guard_time and
life_time_factor. Therefore it
is recommended to overwrite
the life_time_factor with 1
and to select the time
directly via the guard_time
in milliseconds.

100D

h

0 life_time_factor

0

0

1

VAR

UINT8

RW

Ċ

The life_time_factor should
be overwritten with 1 to
select the guard_time
directly.

1010

h

0 store_parameters

ARR

UINT8

RO

Ċ

Not used.

1 save_all_

parameters

00000001

h

00000000

h

{1

h

}

65766173

h

Ċ

UINT32

RW

Ċ

Acceptance of default
parameter set in application
parameter set.

00000000

h

Default parameter set is not
accepted.

65766173

h

Save

Default parameter set is
accepted.

1011

h

0 restore_parameters

ARR

UINT8

RO

Ċ

Query on the number of
possible objects.

1 restore_all_default

_parameters

00000001

h

00000000

h

{1

h

}

64616F6C

h

Ċ

UINT32

RW

Ċ

Loading of the default
parameter set, only possible
if the power stage is
deactivated.
The CAN communication
parameters (node no., baud
rate and operating mode)
remain unchanged.

64616F6C

h

Load

Loading of default parameter
set.

00000001

h

Read access: Reset to default
values.