3 description of the objects, Description of the objects, Canopen communication – Lenze 931K User Manual

Page 55

Advertising
background image

CANopen communication

Node guarding telegram

Description of the objects

5

l

55

KHB 13.0002−EN 4.1

5.9.3

Description of the objects

Index

Name

Possible settings

Characteristics

Lenze

Selection

Description

100C

h

0 guard_time

0

0

{1 ms}

65535

VAR

UINT16

RW

Ċ

For activating the node
guarding monitoring
function, the maximum time
between two remote
requests from the master is
parameterised. The
controller calculates this
time from the product of
guard_time and
life_time_factor. Therefore it
is recommended to overwrite
the life_time_factor with 1
and to select the time
directly via the guard_time
in milliseconds.

100D

h

0 life_time_factor

0

0

1

VAR

UINT8

RW

Ċ

The life_time_factor should
be overwritten with 1 to
select the guard_time
directly.

Advertising