Parameter setting

Position controller (position control function)
Description of the objects

7

l

86

KHB 13.0002−EN 4.1

Characteristics

Possible settings

Name

Index

Description

Selection

Lenze

6065

h

0 following_error_

window

9102

00000000

h

{1 inc}

7FFFFFFF

VAR

UINT32

RW

MAP

Symmetrical range around
the position setpoint.
If the actual position value is
outside the range, a
following error occurs and bit
13 of the status word is set.
Causes for following errors:

l

The drive is blocked

l

The positioning speed is
too high

l

The acceleration values
are too high

l

The value entered for the
following_error_window
index is too low

l

The position controller is
not parameterised
correctly

The unit can be set via the
factor group.

6066

h

0 following_error_

time_out

100

0

{1 ms}

27314

VAR

UINT16

RW

MAP

If the following error lasts
longer than 100 ms, bit 13 of
the status word is set.

60FA

h

0 control_effort

{speed units}

VAR

INT32

RO

MAP

Reading−out of the position
controller correction speed.
The correction speed is the
difference between the set
position and the actual
position with consideration
of the gain.
This value is internally
supplied to the speed
controller as a setpoint.

6067

h

0 position_window

1820

−2

31

{1 inc}

2

31

−1

VAR

UINT32

RW

MAP

Symmetrical range around
the target position. The
target position is reached if
the actual position is within
this range for a certain time.
The unit can be set via the
factor group.

6068

h

0 position_window_

time

0

0

{1 ms}

65535

VAR

UINT16

RW

MAP

If the actual position is within
the position window for as
long as defined here, bit 10 of
the status word is set.