CANopen communication

Process data transfer (PDO transfer)
Activation of the PDOs

5

l

38

KHB 13.0002−EN 4.1

5.3.6

Activation of the PDOs

The following criteria must be met to enable the drive controller to send or receive PDOs:

ƒ

The number_of_mapped_objects object must be non−zero.

ƒ

Bit 31 of the cob_id_used_for_pdos object must be deleted.

ƒ

The communication state of the controller must be operational (see chapter 5.5,
network management).

The following criterion must be met to enable the parameterisation of PDOs:

ƒ

The communication state of the drive controller must not be operational.