5 example of a process data telegram, Example of a process data telegram, Canopen communication – Lenze 931K User Manual

Page 37

Advertising
background image

CANopen communication

Process data transfer (PDO transfer)

Example of a process data telegram

5

l

37

KHB 13.0002−EN 4.1

5.3.5

Example of a process data telegram

The following objects are to be transferred together in a PDO:

ƒ

Status word, index 6041_00

h

(controller control),

ƒ

Modes_of_operation_display, index 6061_00

h

(operating mode)

ƒ

Digital_inputs, index 60FD_00

h

(digital inputs)

The first transmit PDO (TPDO 1) is to be used, and it is always to be sent if one of the digital
inputs changes, but not more often than every 10 ms. The identifier used for this PDO is to
be 187

h

.

1. Delete the number of objects.

Description

Name

Value

To enable the change of the object mapping, the number of
objects has to be set to zero.

number_of_mapped_objects

0

2. Parameterise the objects which are to be mapped.

Description

Name

Value

The objects listed above have to be composed to form a 32−bit
value:

Index = 6041

h

, subindex = 00

h

, length = 10

h

(UINT16)

first_mapped_object

60410010

h

Index = 6061

h

, subindex = 00

h

, length = 08

h

(INT8)

second_mapped_object

60610008

h

Index = 60FD

h

, subindex = 00

h

, length = 20

h

(UINT32)

third_mapped_object

60FD0020

h

3. Parameterise the number of objects.

Description

Name

Value

The PDO has to contain 3 objects

number_of_mapped_objects

3

h

4. Parameterise the transmission mode.

Description

Name

Value

The PDO has to be sent if one or several of the above digital
inputs change.

transmission_type

FF

h

In order to ensure that only changes of the digital inputs cause
the transmission of the PDO, it is masked in such a way that
only the above 16 bits of the object 60FD

h

"come through".

transmit_mask_high

00FFFF00

h

transmit_mask_low

00000000

h

The PDO is to be sent not more often than every 10 ms
(100 × 100

ms).

inhibit_time

64

h

5. Parameterise the identifier.

Description

Name

Value

The PDO is to be sent with the identifier 187

h

. If the PDO is

active, it first has to be deactivated.

Read out the identifier:

cob_id_used_by_pdo

00000181

h

Set bit 31 (deactivate PDO):

cob_id_used_by_pdo

C0000181

h

Write new identifier:

cob_id_used_by_pdo

C0000187

h

Activate PDO by deleting bit 31:

cob_id_used_by_pdo

40000187

h

)

Note!

The parameterisation of the PDO can only be changed if the network state
(NMT) is not operational.