Electrical installation

Electrical connections of CANopen

4

l

13

KHB 13.0002−EN 4.1

4.2

Electrical connections of CANopen

LO

LO

LO

LO

CG

CG

CG

CG

HI

HI

HI

HI

X4.1

X4.1

X4.2

X4.2

A

2

A

1

A

n

PES

PES

PES

PES

CAN-GND

CAN-LOW

CAN-HIGH

120

1 2

3 4 5

6 7 8 9

120

W

120

W

931e_420

Fig. 1

Basic wiring of CANopen with Sub−D connector to the master

A

1

Node 1 − master (e.g. PLC)

A

2

Node 2 − slave (e.g. drive controller 931E)

A

n

Node n − slave, n = max. 127

Specification of the transmission cable

Please observe our recommendations for signal cables.

Bus cable specification

Cable resistance

135 − 165

W/km, (f = 3 − 20 MHz)

Capacitance per unit length

£ 30 nF/km

Loop resistance

< 110

W/km

Wire diameter

> 0.64 mm

Wire cross−section

> 0.34 mm

2

Wires

double twisted, insulated and shielded

ƒ

Connection of the bus terminating resistors:
– One resistor of 120

W each at the first and last bus node

ƒ

Communication protocol
– CANopen (CAL−based communication profile DS 301/DSP 402)

ƒ

Bus extension:
– 40 m for max. data transfer rate of 1 Mbps
– Up to 1 km for reduced data transfer speed

ƒ

Signal level according to ISO 11898

ƒ

Up to 128 bus nodes possible