Commissioning – Lenze 931K User Manual

Page 59

Advertising
background image

Commissioning

Speed control

Parameterising of a process data object (TPDO and RPDO)

6

l

59

KHB 13.0002−EN 4.1

No. Description

Identi

fier

Control

field

Comma

nd code

Index

Subin

dex

Data 1 Data 2 Data 3 Data 4

Data

length

Low

byte

High

byte

1

Network management (NMT)
For the parameterisation of the PDO, the
network management is set to the
’pre−operational’ mode (80

h

).

00

2

80

00

00

00

00

00

00

00

2

Deactivation of the RPDO
The RPDO is deactivated by setting bit
31.

601

8

23

00

14

01

01

02

00

C0

3

Deletion of the number of objects
To enable the changing of the object
mapping, the number of objects
(number_of_mapped_objects) must be
set to zero.

601

5

2F

00

16

00

00

00

00

00

4

Parameterisation of the first object to be
mapped
The index of the object to be mapped
(first_mapped_object) and the length of
the corresponding variable type must be
specified here. The first object to be
mapped is the setpoint speed (index
60FF_00

h

) with a length of 32 bits (20

h

).

601

8

23

00

16

01

20

00

FF

60

5

Definition of the number of objects
In this example, 1 mapped object
(setpoint speed ) is to be transferred
(number_of_mapped_objects).

601

5

2F

00

16

00

01

00

00

00

6

Parameterisation of the transmission
mode
The PDO is to be transferred at cyclic
intervals (FF

h

is entered for the

transmission_type).

601

5

2F

00

14

02

FF

00

00

00

7

Activation of the RPDO
The PDO is activated by cancelling bit
31.

601

8

23

00

14

01

01

02

00

40

8

Network management (NMT)
For the parameterisation of the PDO, the
network management is set to the
’operational’ mode (01

h

).

00

2

01

00

00

00

00

00

00

00

Tab. 3

Example of parameterising a receive PDO