Connecting Your Ultra3000

3-5

Single-Phase Power Wired to Single-Phase Drives

The following examples illustrate grounded single-phase power wired
to single-phase Ultra3000 drives when phase-to-phase voltage is
within drive specifications.

Figure 3.4
Single-Phase Grounded Power Configurations

Note: Reducing transformer output will reduce motor speed.
Note: Feeder and branch short circuit protection is not illustrated.

Isolation Transformer in Grounded Power Configurations

When using an isolation transformer, attach a chassis ground wire to
the neutral connection. This accomplishes the following:

• Prevents the system from floating and thereby avoids any high

voltages that might otherwise occur (e.g., through static).

• Provides a solid earth path for fault conditions.

L1

L2

L1

L2 (Neutral)

TB1

L1

L2/N

L1

L2/N

L1

L2/N

E

TB1

L1

L2

L1

L2

L1

L2/N

E

Transformer Secondary

Transformer Secondary

Ultra3000
Single-Phase
TB1 Terminals

AC Line

Filter

Ultra3000
Single-Phase
TB1 Terminals

Bonded cabinet ground bus

AC Line

Filter

Ground grid or

Power distribution ground

Bonded cabinet ground bus

Ground grid or

Power distribution ground

230V ac

Output

115V ac

Output

ATTENTION

!

If the supply transformer is an auto transformer (not
recommended), a chassis earth ground should not be
added.

A chassis earth ground should already be included
elsewhere in the system, and adding another would
create a short.