Publication 2098-IN003E-EN-P — April 2004

Connecting Your Ultra3000

3-17

3. Locate the TB1 terminal block and remove the plastic cover. Refer

to Understanding Ultra3000 Connectors in Chapter 2 for the front
panel connections of your Ultra3000 drive.

4. Using a screw driver, loosen the screw for each of the terminal

locations and attach wires as shown in the table below.

5. Tighten each terminal screw. Refer to the table on page 3-13 for

torque value.

6. Gently pull on each wire to make sure it does not come out of its

terminal. Re-insert and tighten any loose wires.

7. Re-attach the plastic cover to the terminal block.

IMPORTANT

The auxiliary AC power inputs require dual
element time delay (slow acting) fuses to
accommodate inrush current. Refer to the section
Ultra3000 (230V) Power Specifications in
Appendix A for the inrush current on the
auxiliary AC power input.

If you have this drive:

Insert this wire from
the power supply:

Into this terminal on
TB1:

2098-DSD-005x-xx,
-010x-xx, or -020x-xx

L1

L1

L2

L2/N

Ground

2098-DSD-030x-xx

L1

L1

L2

L2/N

Ground

L1 (auxiliary AC)

L1 AUX

L2 (auxiliary AC)

L2/N AUX

2098-DSD-075x-xx,

-150x-xx

or

2098-DSD-HVxxx-xx,
-HVxxxX-xx

L1

L1

L2

L2

L3

L3

Ground

L1 (auxiliary AC)

L1 AUX

L2 (auxiliary AC)

L2/N AUX

IMPORTANT

The DC bus connections should not be used for
connecting multiple drives together. Contact your
Allen-Bradley representative for further
assistance if the application may require DC
power connections.