Cable categories for the ultra3000 – Rockwell Automation 2090 Ultra3000 Installation Manual User Manual

Page 38

Advertising
background image

Publication 2098-IN003E-EN-P — April 2004

1-14

Installing Your Ultra3000

Observe the following guidelines when installing your 1756-MxxSE
SERCOS interface module (refer to Figure 1.8 for zone locations).

• The clean zone (C) is beneath the less noisy modules (I/O, analog,

encoder, registration, etc. (grey wireway).

• The dirty zone (D) is above and below the power supply and

noisy modules (black wireway).

• The SERCOS fiber-optic cables are immune to electrical noise.

Figure 1.8
Establishing Noise Zones (ControlLogix)

Cable Categories for the Ultra3000

The table below indicates the zoning requirements of cables
connecting to the Ultra3000.

(1)

D

D

C

EMC

Filter

Spare Slot(s)

Dirty Wireway

Clean Wireway

Route dirty wireways directly above the ControlLogix rack

(shielded by the chassis)

EMC filter/power supply
connections segregated
(not in wireway)

Dirty I/O

(24V dc I/O, AC I/O)

Clean I/O

(Analog, Encoder

Registration, etc.)

Wire/Cable

Connector

Zone

Method

Very
Dirty

Dirty

Clean

Ferrite
Sleeve

Shielded
Cable

DC-/DC+

TB1

X

L1, L2, L3 (shielded cable)

X

X

L1, L2, L3 (unshielded cable)

X

U, V, W (motor power)

X

X

Registration Wiring

CN1

X

X

Other 24V Wiring

CN1

X

Motor Feedback

CN2

X

X

Serial Communications

CN3

X

X

Fiber-Optic

Rx and Tx

No Restrictions