Determining your type of input power, Three-phase power wired to three-phase drives – Rockwell Automation 2090 Ultra3000 Installation Manual User Manual

Page 99

Advertising
background image

Publication 2098-IN003E-EN-P — April 2004

Connecting Your Ultra3000

3-3

Determining Your Type of
Input Power

On the following pages are examples of typical single-phase and
three-phase facility input power wired to single-phase and
three-phase Ultra3000 drives.

The grounded power configuration allows you to ground your
single-phase or three-phase power at a neutral point. Match your
secondary to one of the examples and be certain to include the
grounded neutral connection.

Three-Phase Power Wired to Three-Phase Drives

The following examples illustrate grounded three-phase power wired
to three-phase Ultra3000 drives when phase-to-phase voltage is within
drive specifications.

Figure 3.1
Three-Phase Power Configuration (WYE Secondary)

Note: Feeder and branch short circuit protection is not illustrated.

IMPORTANT

The Ultra3000 (2098-DSD-HVxxx) 460V drives are
designed to operate from grounded or ungrounded
power configurations. For systems requiring CE or
for Ultra3000 (2098-DSD-xxx) 230V drives, the
supply must be grounded.

IMPORTANT

Grounded power (WYE secondary) is the preferred
configuration. Examples with delta secondaries
(though not preferred) are also shown.

L1

L2

L3

TB1

L1

L2

L3

E

L1

L2

L3

L1

L2

L3

Bonded Cabinet
Ground Bus

Transformer (WYE) Secondary

Ultra3000

Three-Phase AC Input

TB1 Terminals

Ground Grid or

Power Distribution Ground

AC Line

Filter

Bonded Cabinet
Ground Bus

Ground Grid or

Power Distribution Ground

Advertising
This manual is related to the following products: