Specifications and Dimensions

A-5

Fuse Specifications

Use class CC, G, J, L, R, or T class fuses, with current ratings as
indicated in the table below. The table below lists fuse examples
recommended for use with the Ultra3000 (230V and 460V) drives.

Refer to Power Wiring Requirements in Chapter 3 for input wire size.

1

Bussmann

®

Fuse

Catalog Number

Input
Voltage

Voltage Type

Recommended Fuse

Class CC

1

Class J

1

2098-DSD-005x-xx

230V

Input Power

FNQ-R-6

LPJ-6SP

2098-DSD-010x-xx

FNQ-R-10

LPJ-10SP

2098-DSD-020x-xx

FNQ-R-20

LPJ-20SP

2098-DSD-030x-xx

FNQ-R-30

LPJ-30SP

2098-DSD-075x-xx

FNQ-R-30

LPJ-30SP

2098-DSD-150x-xx

N/A

LPJ-60SP

2098-DSD-xxxx-xx

Auxiliary Input Power

FNQ-R-10

LPJ-10SP

2098-DSD-HV030x-xx

460V

Input Power

KTK-R-5

LPJ-5SP

2098-DSD-HV050x-xx

KTK-R-8

LPJ-8SP

2098-DSD-HV100x-xx

KTK-R-20

LPJ-17-1/2SP

2098-DSD-HV150x-xx

KTK-R-30

LPJ-30SP

2098-DSD-HV220x-xx

N/A

LPJ-35SP

2098-DSD-HVxxxx-xx

Auxiliary Input Power

FNQ-R-10

LPJ-10SP

IMPORTANT

Follow the wire size information as shown in the
Power Wiring Requirements table on page 3-13 and
select the fuse for the appropriate temperature rating
of the wire. Auxiliary input fuses must not exceed
13A.