3-30

Connecting Your Ultra3000

Connecting Your DeviceNet Cable

To wire the DeviceNet connector:

1. Strip 65 mm (2.6 in.) to 75 mm (2.96 in.) of the outer jacket from

the end of the cable, leaving no more than 6.4 mm (0.25 in.) of
the braided shield exposed.

Figure 3.25
Exposing the Braided Shield

2. Wrap the end of the cable with 38 mm (1.5 in.) of shrink wrap,

covering part of the exposed wires and part of the outer jacket.

Figure 3.26
Adding Shrink Wrap

3. Strip 8.1 mm (0.32 in.) of the insulation from the end of each of

the insulated wire.

Trim the last 6.4 mm (0.25 in.) of the bare wires so that the outside
dimension does not exceed 0.17 mm (0.045 in.).

Figure 3.27
Exposing Wire Strands

IMPORTANT

Use caution not to nick, cut, or otherwise
damage strands as you remove the insulation.

6.4 mm

(0.25 in.)

65 mm

(2.6 in.)

Outer Jacket

Braided Shield

38 mm

(1.5 in.)

Outer Jacket

Shrink Wrap

8.1 mm

(0.32 in.)

Outer Jacket

Shrink Wrap