Publication 2098-IN003E-EN-P — April 2004

Ultra3000 Connector Data

2-39

Analog Output

The Ultra3000 includes a single analog output (not supported on the
SERCOS models) that can be configured through software to represent
drive variables. Figure 2.36 shows the configuration of the analog
output.

Figure 2.36
Analog Output Configuration

The following table provides a description of the analog output
specifications.

1

The offset and gain errors of the analog output can be corrected for an application using Ultraware scale and
offset settings.

100

Ω

0.01

μF

AOUT

Ultra3000 Drive

IMPORTANT

Output values can vary during power-up until the
specified power supply voltage is reached.

Parameter

Description

Minimum

Maximum

Resolution

Number of states that the output signal is divided
into, which is 2

(to the number of bits)

.

8 Bits

Output
Current

Current capability of the output.

-2 mA

+2 mA

Output
Signal Range

Range of the output voltage.

-10V

+10V

Offset Error

Deviation when the output should be at 0V.

500 mV

1

Gain Error

Deviation of the transfer function from unity gain,
expressed in a percent of full scale.

10%

1

Bandwidth

Frequency response of the analog output

50 Hz