Bonding Modules

Unless specified, most paints are not conductive and they act as
insulators. To achieve a good bond between modules and the
subpanel, surfaces need to be paint-free or plated. Bonding metal
surfaces creates a low-impedance exit path for high-frequency energy.

Improper bonding blocks that direct exit path and allows
high-frequency energy to travel elsewhere in the cabinet. Excessive
high-frequency energy can effect the operation of other
microprocessor controlled equipment. The illustrations that follow
(refer to Figure 1.5) show details of recommended bonding practices
for painted panels, enclosures, and mounting brackets.

Figure 1.5
Recommended Bonding Practices

IMPORTANT

To improve the bond between the drive and
subpanel, construct your subpanel out of zinc plated
(paint-free) steel.

Stud-mounting the subpanel

to the enclosure back wall

Stud-mounting a ground bus

or chassis to the subpanel

Subpanel

Welded stud

Scrape paint

Flat washer

If the mounting bracket is coated with
a non-conductive material (anodized,
painted, etc.), scrape the material
around the mounting hole.

Star washer

Nut

Nut

Flat washer

Mounting bracket or

ground bus

Use a wire brush to remove paint from
threads to maximize ground
connection.

Back wall of
enclosure

Welded
stud

Subpanel

Star washer

Use plated panels or scrape paint on
front of panel.

Subpanel

Nut

Nut

Star washer

Flat washer

Star washer

Star washer

Scrape paint on both sides of
panel and use star washers.

Tapped hole

Bolt

Flat washer

Ground bus or

mounting bracket

If the mounting bracket is coated with
a non-conductive material (anodized,
painted, etc.), scrape the material
around the mounting hole.

Bolt-mounting a ground bus or chassis to the back-panel