Installing Your Ultra3000

1-7

Ventilation Requirements

This section provides information to assist you in sizing your cabinet
and locating your Ultra3000 drive(s) inside the cabinet.

Figure 1.4
Minimum Clearance Requirements

Refer to Appendix A for Ultra3000 power dissipation specifications.

50.8 mm (2.0 in.) clearance

for airflow and installation

50.8 mm (2.0 in.) clearance

for airflow and installation

Allow 12.7 mm (0.5 in.)

side clearance

Allow 12.7 mm (0.5 in.)

side clearance

Motor cable entry area for ground clamp

Minimum cabinet depth = 243.8 mm (9.6 in.)
Minimum front clearance = 76.2 mm (3.0 in.)

Do not mount drive on its side.

Ultra3000 mounted

vertically on the panel

IMPORTANT

If the cabinet is ventilated, use filtered or
conditioned air to prevent the accumulation of dust
and dirt on electronic components. The air should be
free of oil, corrosives, or electrically conductive
contaminates.