Shunt module power wiring requirements – Rockwell Automation 2090 Ultra3000 Installation Manual User Manual

Page 110

Advertising
background image

Publication 2098-IN003E-EN-P — April 2004

3-14

Connecting Your Ultra3000

Figure 3.14
TB1 Terminal Positions

Shunt Module Power Wiring Requirements

1

75° C (167° F), 600V copper wire. Maximum length 3.05 m (10 ft).

2

105° C (221° F), 600V copper wire (preferred) 90° C (194° F) (minimum). Maximum length 3.05 m (10 ft).

Note: Refer to Figure 3.15 for TB2 terminal positions.

TB1 Terminal Positions

(2098-DSD-005x-xx, -010x-xx,

-020x-xx)

TB1 Terminal Positions

(2098-DSD-030x-xx)

TB1 Terminal Positions

(2098-DSD-075x-xx and

-150x-xx)

TB1 Terminal Positions

(2098-DSD-HVxxx-xx and

-HVxxxX-xx)

Motor Power

Connections

Input Power

Connections

Active Shunt

Connections

DC Bus+

DC Bus-

L1

L2/N

U

V

W

U

V

W

DC Bus+

DC Bus-

L1

L2/N

L1 AUX

L2/N AUX

AC Input

Power

Connections

Motor Power

Connections

U

V

W

DC Bus+

DC Bus-

L1

L2

L3

L1 AUX

L2/N AUX

Motor Power

Connections

AC Input

Power

Connections

DC Bus+

DC Bus-

W

V

U

L3

L2

L1

L1 AUX

L2/N AUX

Motor Power

Connections

AC Input

Power

Connections

Ultra3000 Drives

Shunt Module
Catalog Number

Connects to
Terminals

Recommended
Wire Size
mm

2

(AWG)

Terminal Block
Torque Values
Nm (lb-in.)

2098-DSD-005x-xx, -010x-xx, and
-020x-xx

2090-UCSR-A300

4.0 (12)

1

1.25 (11)

2098-DSD-030x-xx

9101-1183

TB2-1

TB2-2

TB2-3

2.5 (14)

1

2098-DSD-075x-xx and
2098-DSD-150x-xx

2090-UCSR-P900

10 (8)

1

2098-DSD-HV030-xx, -HV030X-xx

-DSD-HV050-xx, and -HV050X-xx

2090-SR120-09

6 (10)

2

2098-DSD-HV100-xx and
-HV100X-xx

2090-SR040-09 or

2090-SR040-18

2098-DSD-HV150-xx and
-HV150X-xx

2090-SR025-09 or

2090-SR025-18

2098-DSD-HV220-xx and
-HV220X-xx

2090-SR020-36

TB1-DC Bus+

TB1-DC Bus-

TB1-L1

TB1-L2/N