Troubleshooting for devicenet drives, Devicenet module status led, Devicenet network status led – Rockwell Automation 2090 Ultra3000 Installation Manual User Manual

Page 138

Advertising
background image

Publication 2098-IN003E-EN-P — April 2004

4-10

Troubleshooting Status Indicators

Troubleshooting for
DeviceNet Drives

DeviceNet Module Status LED

Use the table below for troubleshooting the DeviceNet Module Status
LED on your Ultra3000 (2098-DSD-xxx-DN, -xxxX-DN, -HVxxx-DN, or
-HVxxxX-DN).

DeviceNet Network Status LED

Use the table below for troubleshooting the DeviceNet Network Status
LED on your Ultra3000 (2098-DSD-xxx-DN, -xxxX-DN, -HVxxx-DN, or
-HVxxxX-DN).

If the Module
Status LED is:

Status is:

Potential Cause is:

Possible Resolution is:

Off

Not powered

No power

There is no power going to the device.

Steady-Green

Operational

Normal operation

Normal operation - no action needed.

Flashing-Green

Device is in
stand-by

Processing or waiting
for input

Normal operation - no action needed.

Flashing-Red

Recoverable fault

Not operational

Power cycle or reset the drive.

Steady-Red

Unrecoverable
fault

Drive problem

1. Check drive for power-up error.

2. Replace drive.

Flashing-Red/
Green

Self testing

Self-test in progress

The device is in self test, wait.

If the Network
Status LED is:

Status is:

Potential Cause is:

Possible Resolution is:

Off

• Not powered
• Not on-line

• No power going to

the device

• Failed Duplicate

MAC ID check

1. Check the Module Status LED to verify that the drive is powered.

2. Check that one or more nodes are communicating on the network.

3. Check that at least one other node on the network is operational and the data

rate is the same as the drive.

Flashing-green

• On-line
• Not connected

• Passed Duplicate

MAC ID check

• No connection

established

No action is needed. The LED is flashing to signify that there are no open
communication connections between the drive and any other device. Any connection
(I/O or explicit message) made to the drive over DeviceNet will cause the LED to stop
flashing and remain Steady-ON for the duration of any open connection.

Steady-green

• On-line
• Connected

One or more
connections
established

No action needed. This condition is normal.

Flashing-red

• On-line
• Time-out

I/O connection timed
out

1. Re-initiate I/O messaging by the master controller.

2. Reduce traffic or errors on the network so that messages can get through within

the necessary time frame.

Steady-red

Network Failure

• Failed Duplicate

MAC ID check

• Bus-off

1. Ensure that all nodes have unique addresses.

2. If all node addresses are unique, examine network for correct media installation.

3. Ensure that all nodes have the same Data Rate.