Connecting Your Ultra3000

3-13

Power Wiring
Requirements

Power wiring requirements are given in the tables below. Wire should
be copper with 75

° C (167° F) minimum rating, unless otherwise

noted. Phasing of main AC power is arbitrary and earth ground
connection is required for safe and proper operation.

Ultra3000 Power Wiring Requirements

1

The input power may be optionally isolated through a transformer.

Note: Refer to Figure 3.14 for TB1 terminal positions.

IMPORTANT

The National Electrical Code and local electrical
codes take precedence over the values and methods
provided.

Ultra3000 Drives

Description

Connects to
Terminals
TB1

Recommended
Wire Size
mm

2

(AWG)

Terminal Block
Torque Values
Nm (lb-in.)

2098-DSD-005x-xx

Input Power

1

100-240V ac

single-phase

1.5 (16)

1.25 (11)

2098-DSD-010x-xx

2.5 (14)

2098-DSD-020x-xx

3 (12)

2098-DSD-030x-xx

Input Power

1

100-240V ac

single-phase

6 (10)

2098-DSD-075x-xx

Input Power

1

100-240V ac

three-phase

2098-DSD-150x-xx

10 (8)

4.0 (35)

2098-DSD-HV030x-xx

Input Power

1

230-480V ac

three-phase

2.5 (14)

1.25 (11)

2098-DSD-HV050x-xx

2098-DSD-HV100x-xx

4 (12)

2098-DSD-HV150x-xx

6 (10)

2098-DSD-HV220x-xx

10 (8)

All Ultra3000 drives

(230V and 460V)

Motor Power

Motor power cable
depends on motor/
drive combination.

L1, L2/N, and

L1, L2/N,

L1 AUX,

and L2/N AUX

L1, L2, L3,

L1 AUX,

and L2/N AUX

L3, L2, L1

L1 AUX,

and L2/N AUX

U, V, W, and