Establishing Noise Zones

Observe the following guidelines when laying out your panel (refer to
Figure 1.7 for zone locations).

• The clean zone (C) is above and beneath the Ultra3000 and

includes CN1, CN2, CN3, and the DC filter (grey wireways).

• The dirty zone (D) is left of the Ultra3000 (black wireways) and

includes the circuit breakers, transformer, AC line filter, contactors,
24V dc power supply, and motor power cables.

• The very dirty zone (VD) is limited to where the AC line (EMC)

filter AC output jumpers over to the Ultra3000. Shielded cable is
required only if the very dirty cables enter a wireway.

• The SERCOS fiber-optic cables are immune to electrical noise.

Figure 1.7
Establishing Noise Zones

1

If I/O cable contains (dirty) relay wires, route cable with motor power wires in dirty wireway.

2

This is a clean 24V dc available for CN1 I/O power supply. The 24V enters the clean wireway and exits to the right.

3

This is a dirty 24V dc available for motor brakes and contactors. The 24V enters the dirty wireway and exits to the
left.

(1)

C

D

D

VD

3

2

D

D

C

CN3

CN2

D

CN1 I/O Cable

1

Route Motor Power
Shielded Cable

Route Encoder/Analog/Registration

Shielded Cable

Dirty Wireway

Clean Wireway

Motor Power Cables

24V

Power Supply

Circuit

Breaker

XFMR

AC

Line Filter

DC

Filter

Contactors

Very dirty EMC filter connections

segregated (not in wireway)

Ultra3000

Mount AC line

filter as close

to the drive as

possible

Advertising
This manual is related to the following products: