Installing Your Ultra3000

External Shunt Resistor

Observe the following guidelines when mounting your external shunt
resistor (refer to Figure 1.9 and for an example).

• Mount circuit components and wiring in the very dirty zone or in

an external shielded enclosure. Run shunt power and fan wiring
inside metal conduit to minimize the effects of EMI and RFI.

• Mount resistors (other than metal-clad) in a shielded and

ventilated enclosure outside the cabinet.

• Keep unshielded wiring as short as possible. Keep shunt wiring as

flat to the cabinet as possible.

Figure 1.9
External Shunt Resistor Outside the Enclosure

C

C

VD

1394 Digital Servo Controller

300W Shunt Module

BULLETIN 1394 300W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.

R

D

D

VD

D

D

D

Motor

DC Bus

100-240 VAC

50/60 Hz

L1

AUX

L2/N
AUX

L2/N

L1

-

+

W

V

TB1

External

Shunt

3

2

1

Internal

TB2

U

Dirty Wireway

Clean Wireway

Motor Power Cable

Very dirty shunt connections

segregated (not in wireway).

Maximum Length: 3.05 m (10 ft).

Route Motor Power
Shielded Cable

Route Encoder/Analog/Registration

Shielded Cables

Customer-supplied

metal enclosure

150 mm (6.0 in.) of

clearance on all sides

of the shunt module

minimum

Metal conduit

(where required by local code)

Enclosure

Shunt Wiring Methods:
Twisted pair in conduit (1st choice).

Shielded twisted pair (2nd choice).

Twisted pair, 2 twists per foot min. (3rd choice).

24V

Power Supply

Circuit

Breaker

XFMR

AC

Line Filter

DC

Filter

Contactors

Ultra3000

Very dirty power connections

segregated (not in wireway)